2 signaling contact – Siemens Industrial Ethernet Switches SCALANCE X-200 User Manual

Page 140

background image

Connection

5.2 Signaling contact

SCALANCE X-200

140

Operating Instructions, 12/2011, A5E00349864-19

5.2

Signaling contact

Signaling contact

The signaling contact (relay contact) is a floating switch with which error/fault states can be

signaled by breaking the contact.
The signaling contact is connected to a 2-pin plug-in terminal block.
Exception:

The signaling contact on the SCALANCE X204 IRT PRO and SCALANCE X202-2P IRT

PRO is connected using a 5-pin b-coded M12 socket.

IE Switches X-200

SCALANCE X204 IRT PRO,
SCALANCE X202-2P IRT PRO,
SCALANCE X201-3P IRT PRO

Pin number

Assignment Pin number

Assignment

Pin 1

F1

Pin 1

F1

Pin 2

F2

Pin 2

n. c.

-

-

Pin 3

n. c.

-

-

Pin 4

F2

-

-

Pin 5

n. c.

The following errors/faults can be signaled by the signaling contact:
● The loss and the establishment of a link on a monitored port.
● The failure of one of the two redundant power supplies.
● The loss of the connection to the controller in PROFINET IO mode.
● The redundancy manager signals an error

Note

SCALANCE X204 IRT PRO, SCALANCE X202-2P IRT PRO and SCALANCE X201-3P

IRT PRO have no redundant power supply

● Incompatible C-PLUG was inserted.
The connection or disconnection of a communication node on an unmonitored port does not

lead to an error message.