Siemens Industrial Ethernet Switches SCALANCE X-200 User Manual
Page 184
Configuration / diagnostics using remote mechanisms
6.3 Configuration using Web Based Management (WBM) and Command Line Interface (CLI)
SCALANCE X-200
184
Operating Instructions, 12/2011, A5E00349864-19
Ring Redundancy Manager
Here you can choose whether the "active" status of the redundancy manager triggers an
error.
Standby Manager (only SCALANCE X200IRT)
Here, you can choose whether the "master" status and "passive" or "slave" and "active" or
partner not found triggers an error.
Enable Link Down Monitoring
Error message when the status of the port is "Link down". Here, you can enable/disable
monitoring of the link status for the individual ports.
Enable Link Up Monitoring
Error message when the status of the port is "Link up". Here, you can enable/disable
monitoring of the link status for the individual ports.
Note
With the default setting as supplied, no port is monitored; in other words, the fault mask is
empty.
As default, the power supply is also not monitored.
Syntax of the Command Line Interface
Table 6- 11 Fault Mask - CLI\X200>
Command
Description
Comment
info
Displays information on the "X-200" menu item.
fault
Displays the fault status.
downmask <1-n>
monitoring of a link down event is enabled.
Administrator only.
upmask <1-n>
Specifies a port mask for the ports for which the
monitoring of a link up event is enabled.
Administrator only.
others
Specifies the fault mask for:
P - power mask
Administrator only.