Parameter Settings for Point # 1

With process control equipment disabled, enter the RUN mode to monitor system
performance and alarm programming. Otherwise, perform a Reading Measurement
simulation (P920).

When satisfied with system performance and programming:

connect a high alarm indicator to Relay #1 (see P100 = 4).

connect a low alarm indicator to Relay #2.

connect a high high alarm indicator and filling equipment stop/start control to
Relay #3.

connect a low low alarm indicator to Relay # 4.

(Note that relays are de-energized in power off and alarm conditions).

For cement applications (or any very dusty dry solids), measurement difficulties during
vessel filling are common. For this example (assume the maximum filling rate), failsafe
operates as follows:

e.g.

Number

Description

Instructions

P001

Operation

Enter "1" for

level

.

P002

Material

Enter "2" for

solid

.

P003

Measurement Response

Enter "1" for

slow

(0.1 m/min).

P004

Transducer

Enter "107" for

XLT-30

.

P005

Units

No entry required, (preset for

metres

).

P006

Empty

Enter "30" for transducer face to Empty equals

30.00

metres

.

P007

Span

No entry required, (preset to

29.01 metres

).

P070

Failsafe Timer

Enter "2" for failsafe activation after

2 minutes

without

a valid echo.

P071

Failsafe Material Level

Enter "HI" for

advance to Span on "LOE"

.

P072

Failsafe Advance

No entry required. (preset to

restricted

).

P100

Relay Set Up

Enter "4" for

High, Low, High High, and Low Low

alarm

relays.

P101

High

Alarm

Enter "25" for

High

Alarm at

25.00 m

.

P102

Low

Alarm

Enter "10" for

Low

Alarm at

10.00 m

.

P103

High

High

Alarm

Enter "27" for

High

High

Alarm at

27.00 m

.

P104

Low

Low

Alarm

Enter "5" for

Low

Low

Alarm at

5.000 m

.

09:15 am

Echo lost at 6.00 m, low alarm is still on, failsafe coundown begins

09:17 am

Failsafe activated,

actual level = 6.16 m,

reported level = 6.00 m.

09:57 am

Low alarm off,

actual level = 9.36 m,

reported level = 10.00 m.

12:27 am

High alarm on,

actual level = 21.36 m,

reported level = 25.00 m.

12:47 am

Infeed stopped,

actual level = 22.96 m,

reported level = 27.00 m.