beautypg.com

P801 range extension, P802 transducer with submergence shield, P803 shot / pulse mode – Siemens sitrans LU01 User Manual

Page 74

background image

Page 68

SITRANS LU01 – INSTRUCTION MANUAL

7ML19985BE02

Pa

ra

m

e

te

rs

Use this feature if the surface is reported to be near the transducer face but is in fact
much further away. Extend this value when changing transducer location, mounting, or
aiming.

Please note that changing the Near Blanking cannot correct measurement problems.
Ensure that Span (P007) < Empty (P006) minus Near Blanking (P800).

P801 Range Extension

Used if incorrect level is reporated (when material level is lower than Empty, P006).

Range extension is the distance in Units (P005) or % of Span (P007) beyond Empty, which
is still ultrasonically measureable. If empty is substantially higher than the actual vessel
bottom, increase Range Extension such that Empty plus Range Extension is greater than
the transducer to vessel bottom distance.

P802 Transducer with Submergence Shield

Used when the transducer is expected to be submerged on occasion.

When a transducer with a submergence shield is submerged, the shield traps an air
pocket that creates a special echo. The SITRANS LU01 recognizes the echo and
advances the reading to the highest level and operates displays and outputs accordingly.
This feature is effective for when power is returned while the transducer is submerged.

P803 Shot / Pulse Mode

Determines what type of ultrasonic shots are fired.

Values

Range: 0.000 to 9999
Preset: 20% of Span (P007)

Related

P005 Units

P006 Empty

P007 Span

P004 Transducer

Values

0

*

Off

1

Submergence transducer

Related

P006 Empty

P071 Failsafe Material Level

Relays

Values

1

Short

2

*

Short and long

Related

P006 Empty

P805 Echo Confidence

P804 Confidence Threshold

P852 Short Shot Range