For IN-BOUNDS and OUT-OF-BOUNDS Relay Functions (P111 = 2 and 3 respectively), a
dead band prevents relay chatter due to material level fluctuations at both the upper and
lower setpoints.

Independent Relay Failsafe (P129)

P129 Relay Failsafe

Sets the failsafe operation per relay to allow for more flexible programming.

Use this for operations independent of the Failsafe Material Level (P070).

Relay Failsafe is only available for the following relay functions (P111) and is not used for
any other relay control function.

To select an independent Relay Failsafe value:

1.

Press FUNCTION

to display the Auxiliary Function symbol.

2.

Press ARROWS

to scroll through the failsafe options.

3.

Select option and press ENTER

.

Enter the dead band in either percent of
span or units of measure (P005). The
deadband value is applied both above
and below the upper and lower bound
setpoints as shown in the figure.

Primary Index

Relay

Values

OFF

*

Response governed by P071 Failsafe Material Level

HOLd

For LAST KNOWN relay state retention

dE

To have the relay de-energize immediately on failsafe

En

To have the relay energize immediately on failsafe

Altered by

P071 Failsafe Material Level

Related

P070 Failsafe Timer

P111 Relay Control Function

Relay Function (P111)

Preset (P129)

1 – level alarm

OFF

2 – in bounds alarm
3 – out of bounds alarm
4 – rate of change alarm
5 – temperature alarm
50 – all pump controls

dE

Actual ON or OFF setpoint

Actual OFF or ON setpoint

P116, deadband

P116, deadband

Setpoint set in P112 or P113