beautypg.com

P833 tvt start min, P834 tvt start duration, P835 tvt slope min – Siemens sitrans LU01 User Manual

Page 83

background image

7ML19985BE02

SITRANS LU01 – INSTRUCTION MANUAL

Page 77

m

mmmm

Pa
ra

m

e

te

rs

6.

Press ARROWS

to change the bias value of the breakpoint, –50 to 50.

7.

Press ENTER

.

8.

Press TRANSDUCER

to update the scope display with the new TVT.

P833 TVT Start Min

Use this feature to adjust the TVT Curve height to ignore false echoes (or pick up true

echoes) near the start of the Echo Profile.

Enter the minimum TVT Curve start point (in dB above 1 μV rms).

This feature should only be used if increased Near Blanking (P800) would extend farther
than desired into the measurement range.

P834 TVT Start Duration

Use this feature in conjunction with TVT Start Min (P833) to ignore false echoes (or pick

up true echoes) near the start of the Echo Profile.

Enter the time (in ms) for the TVT Curve to decrease from the TVT Start Min (P833) point
to the TVT Curve baseline.

P835 TVT Slope Min

Enter the minimum slope (in dB/s) for the middle of the TVT Curve.

Use this feature to adjust the slope declination, and use it in conjunction with TVT Start
Duration (when a long flat TVT Type is selected) to ensure the TVT Curve remains above
the false echoes in the middle of the Echo Profile. Alternatively, if TVT Type is set for TVT
Slopes (P830 = 6), preset is 2000. Use this parameter to adjust the slope declination when
TVT type is set to TVT slopes (P830=6).

Values

Range: -30 to 225
Preset: 50

Related

P800 Near Blanking

P834 TVT Start Duration

Values

Range: 0 to 9999
Preset: 30

Related

P833 TVT Start Min

P835 TVT Slope Min

Values

Range: 0 to 9999
Preset: 200

Related

P830 TVT Type

P834 TVT Start Duration