If Temp Source (P660) is set to any value other than Fixed Temp, the value displayed is the
temperature measured. If Temp Source is set to Fixed Temp, the P661 value is displayed.

Rate (P700 to P707)

These parameters determine how material level changes are reported.

P700 Max Fill Rate

Adjusts the SITRANS LU01 response to increases in the actual material level (or advance

to a higher Failsafe Material Level, P071).

Enter a value slightly greater than the maximum vessel filling rate. This value, in Units
(P005) or % of Span (P007) per minute, is automatically altered when Maximum Process
Speed (P003) is altered.

P701 Max Empty Rate

Adjusts the SITRANS LU01 response to decreases in the actual material level (or advance

to a lower Failsafe Material Level, P071).

Enter a value slightly greater than the maximum vessel emptying rate. This value, in Units
(P005) or % of Span (P007) per minute, is automatically altered when Maximum Process
Speed (P003) is altered.

Values

Range: 0.000 to 9999

Altered by

P003 Maximum Process Speed

Related

P005 Units

P007 Span

P071 Failsafe Material Level

P003 Value

Meters/Minute

1

0.1

2

1

3

10

Values

Range: 0.000 to 9999

Altered by

P003 Maximum Process Speed

Related

P005 Units

P007 Span

P071 Failsafe Material Level

P003 Value

Meters / Minute

1

0.1

2

1

3

10