P051 Maximum Volume
For Readings in volumetric units (rather than percent), enter the vessel volume between
Empty (P006) and Span (P007).
Any volume units can be chosen because volume is calculated from empty to maximum
span and is scaled according to the Tank Shape (P050) value.
Values
7
Parabola Ends
8
Sphere
9
Universal Linear
10
Universal Curved
Alters
•
P001 Operation
•
P051 Maximum Volume
•
P920 Reading Measurement
Values
Range: 0.000 to 9999
Preset: 100.0
Alters
P060 Decimal Position
Related
•
P006 Empty
•
P007 Span
•
P924 Volume Measurement
Note:
Make sure selected chosen units allow LCD volume display.
Examples:
If max. volume = 3650 m
3
, enter 3650
If max. volume = 267500 gallons, enter 267.5 (thousands of gallons)