beautypg.com

P711 echo lock, P712 echo lock sampling – Siemens sitrans LU01 User Manual

Page 67

background image

7ML19985BE02

SITRANS LU01 – INSTRUCTION MANUAL

Page 61

m

mmmm

Pa
ra

m

e

te

rs

P711 Echo Lock

Use this feature to select the measurement verification process.

If a material agitator (mixer) is used in the vessel monitored, set Echo Lock for maximum
verification or material agitator to avoid agitator blade detection. Ensure the agitator is
always ON while the SITRANS LU01 is monitoring the vessel to avoid stationary blade
detection.

When set for max verification or material agitator, a new measurement outside of the
Echo Lock Window (P713) must meet the sampling criterion (P712).

For total lock, Echo Lock Window (P713) is preset to zero 0. The SITRANS LU01
continuously searches for the best echo according to the algorithm chosen (P820). If the
selected echo is within the window, the window is then centered about the echo. If not,
the window widens with each successive shot until the selected echo is within the
window. The window then returns to its normal width.

When Echo Lock is OFF , the SITRANS LU01 responds immediately to a new
measurement as restricted by the Max Fill / Empty Rate (P700 / P701); however,
measurement reliability is affected.

P712 Echo Lock Sampling

The sampling criterion sets the number of consecutive echoes appearing above or below

the echo currently locked onto, that must occur before the measurements are validated

as the new reading (for Echo Lock P711 values: 1 or 2).

Values

0

Off

1

Maximum verification

2

*

Material agitator

3

Total lock

Related

P700 Max Fill Rate

P701 Max Empty Rate

P712 Echo Lock Sampling

P713 Echo Lock Window

P820 Algorithm

Values

Range: 1:1 to 99:99
Format: x:y
x = the number of above echoes
y = the number of below echoes

Related

P711 Echo Lock

P711 value

P712 preset value

1, max verification

5:5

2, material agitator

5:2