beautypg.com

Relays (p100 to p119), P072 failsafe level advance – Siemens sitrans LU01 User Manual

Page 45

background image

7ML19985BE02

SITRANS LU01 – INSTRUCTION MANUAL

Page 39

m

mmmm

Pa
ra

m

e

te

rs

Relay reaction

The way in which relay programming reacts to the failsafe level depends on P129 Relay
Failsafe (page 46). By default:

Alarm relays have P129 = OFF and so react to the Failsafe Material Level.

Control relays have P129 = dE and so de-energize the relay when the unit enters
Failsafe mode regardless of the Failsafe Material Level.

P072 Failsafe Level Advance

Sets the speed the SITRANS LU01 advances to and returns from the Failsafe Material

Level.

Relays (P100 to P119)

The SITRANS LU01 has four relays (or digital outputs) used to control devices and alarms.
While the number of devices is limited by the relays, all control functions are accessible
through software and each parameter is indexed to the relays.

The SITRANS LU01 makes standard application programming easier by providing an
extensive list of presets in P100 (Preset Applications).

Standard alarms are set from P101 to P104. In the RUN mode, when the material level:

rises to a High or High High Alarm value, the associated Alarm and Relay Status
indicators are displayed and the allocated relay(s) de-energize.

falls 5% of Span (P007) below the High or High High Alarm value, the associated
Alarm and Relay Status indicators extinguish, and the allocated relay(s) energize.

falls below the Low or Low Low Alarm value, the associated Alarm and Relay Status
indicators are displayed and the allocated relay(s) de-energize.

rises 5% of Span (P007) above the Low and Low Low Alarm value, the associated
Alarm and Relay Status indicators extinguish, and the allocated relay(s) energize.

To display the current value (or enter a new value) in percent of Span, press

as

required to display the % symbol.

Control functions allow each relay to be configured independently to take advantage of
the SITRANS LU01’s advanced features and flexibility. Start with a preset application and
then change the required parameters to make the task more efficient.

Values

1

* Restricted

Advances to/from Failsafe Material Level as set by
P003, P700 and P701.

2

Immediate Failsafe Material Level assumed immediately

3

Fast Back

Failsafe Level Advance is restricted, return is
immediate

Related

P003 Maximum Process Speed

P070 Failsafe Timer

P071 Failsafe Material Level

P700 Max Fill Rate

P701 Max Empty Rate

Note:

Enter all standard alarm material level values in Units (P005) or percent of

Span (P007) as referenced to Empty (P006).