beautypg.com

Installation, Sitrans lu01, Location – Siemens sitrans LU01 User Manual

Page 15: Cable/conduit entry requirements, Location cable/conduit entry requirements

background image

7ML19985BE02

SITRANS LU01 – INSTRUCTION MANUAL

Page 9

mm

mmm

Inst

allat

ion

Installation

Installation shall only be performed by qualified personnel, and in accordance with local
governing regulations.

The following procedure applies to all SITRANS LU01 level monitor installations. See
Application Examples on page 89 for additional installation requirements. Also, refer to
the instruction manuals of all other equipment connected to the SITRANS LU01 for
additional installation instructions.

SITRANS LU01

Location

Recommended

Ambient temperature is always within -20 to 50 °C (-5 to 122 °F)

SITRANS LU01 display window is at shoulder level, unless most interaction is
through a SCADA system

Easy access for hand programmer is provided

Cable length requirements are minimal

Mounting surface is free from vibration

Leave sufficient room to swing unit lid open and have clear access.

A place for a laptop computer is provided for on-site Dolphin Plus configuration

Avoid

Exposure to direct sunlight. (Provide a sun shield to avoid direct sunlight.)

Proximity to high voltage/current runs, contacts, SCR or variable frequency motor
speed controllers

Cable/Conduit Entry Requirements

Enclosure cable/conduit entries may be required for:

Transducers

TS-3 temperature sensor (if used)

mA output (if used)

Relays (if used)

Synchronization (see Interconnection/Level System Synchronization)

Power

Communications:

SmartLinx, RS-485, RS-232, bipolar.

Note:

Transducer cables must be run in a grounded metal conduit, separate from

other wiring, (except TS-3 temperature sensor wiring, if applicable).