beautypg.com

Ma output (p200 to p219), P200 ma output range, P201 ma output function – Siemens sitrans LU01 User Manual

Page 53: P203 ma output value / transducer

background image

7ML19985BE02

SITRANS LU01 – INSTRUCTION MANUAL

Page 47

m

mmmm

Pa
ra

m

e

te

rs

mA Output (P200 to P219)

When an mA Output Parameter is accessed, the mA symbol is displayed in the Index Type
field and the mA output number (corresponding to the SITRANS LU01 terminals) is
displayed in the Index field.

P200 mA Output Range

Determines the mA output range.

If either 1 or 2 is selected, the mA output is directly proportional to the mA Function. If
either 3 or 4 is selected, then the output is inversely proportional.

P201 mA Output Function

Alters the mA output/measurement relationship.

P203 mA Output Value / Transducer

Displays current mA output value.

This displays as an Auxiliary Reading when

key is pressed in the RUN mode and

does not include adjustments made using Trim features (P214 / P215).

Primary Index

mA output

Values

0

off

1

0 to 20 mA

20 mA = high level (unless P001 = 2
or 3, then 20 mA = low)

2

*

4 to 20 mA

3

20 to 0 mA

20 mA = low level (unless P001 = 2
or 3, then 20 mA = high)

4

20 to 4 mA

Related

P911 mA Output Value

Primary Index

mA output

Values

value

mA function

Operation (P001)

0

OFF

1

level

level

2

space

space

3

distance

distance

4

volume

Related

P202 mA Output Allocation

P911 mA Output Value

Altered By

P001 Operation

Values

Range: 0.000 to 22.00 (view only)

Note:

This parameter is applicable only if any mA output has the transducer

Index Number as its input source (see P201).