beautypg.com

Test (p900 to p913), P851 short shot floor, P852 short shot range – Siemens sitrans LU01 User Manual

Page 86: P900 software revision number

background image

Page 80

SITRANS LU01 – INSTRUCTION MANUAL

7ML19985BE02

Pa

ra

m

e

te

rs

P851 Short Shot Floor

Enter the minimum echo strength (in dB above 1 μV rms) derived from a short shot to be

considered for evaluation.

P852 Short Shot Range

Enter the maximum distance in Units (P005) to be measured using short shot echoes.

This feature is automatically altered when Transducer (P004) is altered.

Test (P900 to P913)

P900 Software Revision Number

View the EPROM Rev. #.

P901 Memory

Press ENTER

to activate the SITRANS LU01 memory test.

Values

Range: 30 to 100
Preset: 50

Related

P840 Short Shot Number

P842 Short Shot Frequency

P844 Short Shot Width

P850 Short Shot Bias

P852 Short Shot Range

Values

Range: 0.000 to 9999

Altered By

P004 Transducer

Related

P840 Short Shot Number

P842 Short Shot Frequency

P844 Short Shot Width

P850 Short Shot Bias

P851 Short Shot Floor

Note:

These parameters are for Siemens Milltronics service personnel only.

Values

Range: 00.00 to 99.99 (view only)

Values

Display: view only
PASS

(memory test successful)

F1

RAM

F2

NOVRAM

F3

EEPROM

F4

EPROM