beautypg.com

Application examples – Siemens sitrans LU01 User Manual

Page 95

background image

7ML19985BE02

SITRANS LU01 – INSTRUCTION MANUAL

Page 89

mm

mmm

Te

c

hnical Ref

e

re

nce

The Process Speed setting automatically adjusts various parameters affecting the
SITRANS LU01 response to material level changes as in the table that follows.

* Scan Delay (P727) is globally set for all Point Numbers to the value associated with the
fastest Measurement Response (P003) selected for Point Number 1or 2.

Application Examples

The following examples describe the use of SITRANS LU01 programmable features, to
meet the needs of specific process measurement requirements.

It is highly unlikely that your specific installation will match one of these examples
exactly.

However, by reviewing the example (or combination of examples) that matches your
installation best, the relationship between SITRANS LU01 features and process
measurement requirements may be more easily recognized.

Parameter

Values Dependent on Measurement Response

(P003) Value

#

Name (Units)

1(slow)

2(medium) 3(fast)

4(surge)

(5imm.)

P070 Failsafe Timer (min)

100

10

1

0.1

0

P700 Max Fill Rate (m/min)

0.1

1

10

100

1000

P701 Max Empty Rate (m/min)

0.1

1

10

100

1000

P702 Filling Indicator (m/min)

0.01

0.1

1

10

100

P703 Emptying Indicator (m/min) 0.01

0.1

1

10

100

P704 Rate Filter (option)

4

3

2

2

2

P710 Fuzz Filter (% of P007)

100

50

10

1

0

P711 Echo Lock (option)

1 or 2 (dependent on Material (P002)

P713 Echo Lock Window

(dependent on P701/P702 and time since last valid measure-
ment)

P728 Shot Delay (s)

0.5

0.5

0.5

0.2

0.1

P803 Shot/Pulse Mode (option)

2

2

2

1

1

P841 Long Shot Number (qty)

10

5

2

1

1

Example #

Description

1

Level (or Material Volume) Measurement for a single vessel.

2

Space (or Remaining Vessel Capacity) Measurement for a single vessel.