P819 Profile Pointer Amplitude

The amplitude (in dB above 1 μV) of the Echo Profile at the Pointer position.

P820 Algorithm

Chooses the algorithm to generate the measured value from the profile.

Use this to select the algorithm(s) the Sonic Intelligence echo selection is based on. Use
P805 Echo Confidence (page 69) to determine which algorithm gives the highest
confidence under all level conditions. If the wrong echo is processed, observe the echo
processing displays and select an alternate algorithm, either by entering the numeric
value desired, or as below:
1.

Press MEASURE

to display the Auxiliary Function symbol.

2.

Press ARROWS

to access the desired Reading display symbols.

3.

Press ENTER

when the required algorithm is displayed.

Values

Range: 00 to 99 (view only)

Related

P817 Profile Pointer Time

P818 Profile Pointer Distance

P820 Algorithm

P821 Spike Filter

P822 Narrow Echo Filter

P823 Reform Echo

P825 Echo Marker Trigger

Values

1

ALF = long range Area, Largest, and First average (general pur-
pose, solids)

2

A = long range Area only (coarse, heaped solids)

3

L = long range Largest only (liquids, open vessels)

4

F = long range First only (liquids, closed vessel)

5

AL = long range Area and Largest average (fine heaped solids)

6

AF = long range Area and First average (coarse flat solids)

7

LF = long range Largest and First average (general purpose,
liquids)

8

* bLF = short range Largest or First (general purpose)

9

bL = short range Largest only (solids and open vessel liquids)

10

bF = short range First only (closed vessel liquids)

Related

P805 Echo Confidence

P817 Profile Pointer Time

P818 Profile Pointer Distance

P819 Profile Pointer Amplitude

P821 Spike Filter

P822 Narrow Echo Filter

P823 Reform Echo

P825 Echo Marker Trigger