Quick Start (P001 to P007)
P001 Operation
Sets the type of measurement required for the application.
P002 Material
Specifies material type. If the material presents a flat surface perpendicular to the
transducer beam, select liquid.
P003 Maximum Process Speed
Determines level change reaction speed.
Use a setting just fast enough to keep up with your process. Slower settings provide
higher accuracy. Faster settings allow for more level fluctuations.
Values
0
Out-of-service
1
Level – how full the vessel is (Point 1 and/or 2 only)
2
Space – how empty the vessel is (Point 1 and/or 2 only)
3
*
Distance – distance from transducer to material (Point 1 and/
or 2 only)
Values
1
*
Liquid or flat surface
2
Solid or angled surface
Alters
•
P830 TVT Type
Values
1
Slow (0.1 m/min)
2
*
Medium (1 m/min)
3
Fast (10 m/min)
4
Surge (1.7 m/sec)
5
Immediate (17 m/sec)
Alters
•
P070 Failsafe Timer
•
P700 Max Fill Rate
•
P701 Max Empty Rate
•
P702 Filling Indicator
•
P703 Emptying Indicator
•
P704 Rate Filter
•
P710 Fuzz Filter
•
P713 Echo Lock Window
•
P727 Scan Delay
•
P841 Long Shot Number
Related
•
Failsafe (P070 to P072)
•
Rate (P700 to P708)
•
Measurement Verification (P710 to P713)
•
Transducer Scanning (P726 to P729)
•
P905 Transmit Pulse