SITRANS LU01 – INSTRUCTION MANUAL

7ML19985BE02

Pa

ra

m

e

te

rs

* Values shown are for illustration purposes only. Enter values which apply to your

particular installation.

!

2% factory set deadband, adjustable via P116

Setpoints

Action

When

ON OFF Status Alarm

Relay

Level H or HH 85% 70%

On

On

de-energizes

Level rises to 85%

Off

Off

energizes

Level falls to 70%

Level L or LL

15% 30%

On

On

de-energizes

Level falls to 15%

Off

Off

energizes

Level rises to 30%

In bounds

!

80% 50%

On

On

de-energizes

Level falls to 78%

Off

Off

energizes

Level rises to 82%

On

On

de-energizes

Level rises to 52%

Off

Off

energizes

Level falls to 48%

Out of bounds

!

80% 50%

Off

Off

energizes

Level falls to 78%

On

On

de-energizes

Level rises to 82%

Off

Off

energizes

Level rises to 52%

On

On

de-energizes

Level falls to 48%

Rate of change +10% +5%

Off

Off

de-energizes

Fill rate increases to 10%/min

On

On

energizes

Fill rate decreases to 5%/min

-10% -5%

Off

Off

de-energizes Empty rate increases to 10%/min

On

On

energizes

Empty rate decreases to 5%/min

Temperature

60

55

On

On

de-energizes

Temperature rises to 60°C

Off

Off

energizes

Temperature falls to 55°C

-30

-25

On

On

de-energizes

Temperature falls to -30°C

Off

Off

energizes

Temperature rises to -25°C

Pump

80% 20%

On

On

energizes

Start pump down on level at 80%

Off

Off

de-energizes Stop pump down on level at 20%

20% 80%

On

On

energizes

Start pump up on level at 20%

Off

Off

de-energizes

Stop pump up on level at 80%