Cycle and reaction times

5.2 Cycle time

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

5-9

Maximum cycle time

In

STEP 7 you can modify the default maximum cycle time. OB80 is called on when this time

expires. In this block you can specify the CPUs response to this timeout error. The CPU

switches to STOP mode if OB80 does not exist in its memory.

5.2.4

Communication load

Configured communication load for PG/OP communication, S7 communication and CBA

The CPU operating system continuously provides a specified percentage of total CPU

processing performance (time-sharing technology) for communication tasks. Processing

performance not required for communication is made available to other processes. In HW

Config, you can specify a communication load value between 5% and 50%. Default value is

20%.
You can use the following formula for calculating the cycle time extension factor:

100 / (100 – configured communication load in %)

Interruption
of user program

Share can be configured
between 5 % and 50 %

Time slice (1 ms)

Example: 20 % communication load

In your hardware configuration, you have specified a communication load of 20 %. The

calculated cycle time is 10 ms. Using the above formula, the cycle time is extended by the

factor 1.25.

Example: 50 % communication load

In your hardware configuration, you have specified a communication load of 50%. The

calculated cycle time is 10 ms. Using the above formula, the cycle time is extended by the

factor 2.