beautypg.com

Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 177

background image

Technical data of CPU 31x

7.3 CPU 314

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

7-11

Technical data

Number of entries (not configurable)

Max. 100

Communication functions
PG/OP communication

Yes

Global data communication

Yes

Number of GD circuits

4

Number of GD packets

Sending stations

Receiving stations

Max. 4
Max. 4
Max. 4

Length of GD packets

Consistent data

max. 22 bytes
22 bytes

S7 basic communication

Yes

User data per request

Consistent data

max. 76 bytes
76 bytes (for X_SEND or X_RCV)
64 bytes (for X_PUT or X_GET as the server)

S7 communication

Yes

As server

Yes

as client

Yes (via CP and loadable FBs)

User data per request

Consistent data

Max. 180 (for PUT/GET)
64 bytes

S5-compatible communication

Yes (via CP and loadable FCs)

Number of connections

12

can be used for

PG communication

Reserved (default)

Configurable

Max. 11
1
1 to 11

OP communication

Reserved (default)

Configurable

Max. 11
1
1 to 11

S7-based communication

Reserved (default)

Configurable

Max. 8
8
0 to 8

Routing

No

Interfaces
1st interface
Type of interface

Integrated RS485 interface

Physics

RS 485

electrically isolated

No

Interface power supply

(15 to 30 VDC)

max. 200 mA

Functionality

MPI

Yes

PROFIBUS DP

No

Point-to-point communication

No