Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual
Page 89
Cycle and reaction times
5.2 Cycle time
CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05
5-7
Operating system processing time at the scan cycle checkpoint
The table below shows the operating system processing time at the scan cycle checkpoint of
the CPUs. These times are calculated without taking into consideration times for:
•
Testing and commissioning routines, e.g. status/controlling of variables or block status
functions
•
Transfer and deletion of blocks, compressing user program memory
•
Communication
•
Read/write access to the MMC, using SFC82 to 84
Table 5-6
Operating system processing time at the scan cycle checkpoint
CPU
Cycle control at the scan cycle check point (CCP)
312C
500 μs
313C
500 μs
313C-2
500 μs
314C-2
500 μs
312
500 μs
314
500 μs
315
500 μs
317
150 μs
Extension of the cycle time as a result of nested interrupts
Enabled interrupts also extend cycle time. Details are found in the table below.
Table 5-7
Extended cycle time due to nested interrupts
Interrupt type Process
interrupt
Diagnostic
Interrupt
Time-of-day
interrupt
Delay interrupt
Watchdog
interrupt
312C
700 μs
700 μs
600 μs
400 μs
250 μs
313C
500 μs
600 μs
400 μs
300 μs
150 μs
313C-2
500 μs
600 μs
400 μs
300 μs
150 μs
314C-2
500 μs
600 μs
400 μs
300 μs
150 μs
312
700 μs
700 μs
600 μs
400 μs
250 μs
314
500 μs
600 μs
400 μs
300 μs
150 μs
315
500 μs
600 μs
400 μs
300 μs
150 μs
317
190 μs
240 μs
200 μs
150 μs
90 μs
The program runtime at interrupt level must be added to this time extension.