Memory concept

4.1 Memory areas and retentivity

CPU 31xC and CPU 31x, Technical data

4-4

Manual, Edition 08/2004, A5E00105475-05

Retentive behavior of a DB for CPUs with firmware >= V2.1.0

For these CPUs you can specify in STEP 7 (beginning with version 5.2 + SP 1), or at SFC 82

CREA_DBL (parameter ATTRIB -> NON_RETAIN bit), whether a DB at POWER ON/OFF or

RUN-STOP

keeps the actual values (retentive DB), or

accepts the initial values from load memory (non-retentive DB)

Table 4-3

Retentive behavior of DBs for CPUs with firmware >= V2.1.0

At POWER ON/OFF or restart (warm start) of the CPU, the DB should
receive the initial values

(non-retentive DB)

retain the actual values (retentive DB)

Background:
At POWER ON/OFF and restart (STOP-

RUN) of the CPU, the actual values of the

DB are non-retentive. The DB receives the

start values from load memory.

Background:
At POWER OFF/ON and restart (STOP-RUN) of the

CPU, the actual values of the DB are retained.

Requirement in STEP 7:

The "Non-retain" check box must be set

in the block properties of the DB, or

a non-retentive DB was generated with

SFC 82 "CREA_DBL" and the

corresponding block attribute (ATTRIB -

> NON_RETAIN bit.)

Requirement in STEP 7:

The "Non-retain" check box must be reset in the

block properties of the DB or

a retentive DB was generated with SFC 82.

Note
Note that only 256 KB of RAM can be used for retentive data blocks on a CPU 317. The

remainder of the RAM is used by code blocks and non-retentive data blocks.