beautypg.com

Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 123

background image

Technical data of CPU 31xC

6.3 CPU 313C

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

6-13

Technical data
Integrated I/O

Default addresses of the integrated

Digital inputs

Digital outputs

Analog inputs

Analog outputs


124.0 to 126.7
124.0 to 125.7
752 to 761
752 to 755

Integrated functions

Counters

3 channels (see the Manual

Technological

Functions

)

Frequency counters

3 channels, max. 30 kHz (see the Manual

Technological Functions

)

Pulse outputs

3 channels for pulse width modulation, max. 2.5

kHz (see the Manual

Technological Functions

)

Controlled positioning

No

Integrated "Controlling" SFB

PID controller (see the Manual

Technological

Functions

)

Dimensions
Mounting dimensions W x H x D (mm)

120 x 125 x 130

Weight

660 g

Voltages and currents
Power supply (rated value)

24 VDC

Permitted range

20.4 V to 28.8 V

Current consumption (no-load operation)

Typically 150 mA

Inrush current

Typically 11 A

Power consumption (nominal value)

700 mA

I

2

t

0.7 A

2

s

External fusing of power supply lines

(recommended)

LS switch Type C min. 2 A,
LS switch Type B min. 4 A,

Power loss

Typically 14 W

Reference

In Chapter

Specifications of the integrated I/O you can find

the specifications of integrated I/O under

Digital inputs of CPUs 31xC, Digital outputs of

CPUs 31xC, Analog inputs of CPUs 31xC and Analog outputs of CPUs 31xC.

the block diagrams of the integrated I/Os under

Arrangement and usage of integrated

I/Os.