beautypg.com

Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 170

background image

Technical data of CPU 31x

7.2 CPU 312

CPU 31xC and CPU 31x, Technical data

7-4

Manual, Edition 08/2004, A5E00105475-05

Technical data
Data areas and their retentivity
Flag bits

128 bytes

Retentive memory

Yes

Default retentivity

MB0 to MB15

Clock flag bits

8 (1 byte per flag bit)

Data blocks

511
(DB 1 to DB 511)

Length

16 KB

Local data per priority class

max. 256 bytes

Blocks
Total

1024 (DBs, FCs, FBs)
The maximum number of blocks that can be

loaded may be reduced if you are using another

MMC.

OBs

See the Instruction List

Length

max. 16 KB

Nesting depth

Per priority class

8

additional within an error OB

4

FBs

Max. 512
(FB 0 to FB 511)

Length

max. 16 KB

FCs

Max. 512
(FC 0 to FC 511

Length

max. 16 KB

Address areas (I/O)
Total I/O address area

1024 bytes /1024 bytes

(can be freely addressed)

I/O process image

128 bytes/128 bytes

Digital channels

Max. 256

of those local

Max. 256

Analog channels

Max. 64

of those local

Max. 64

Assembly
Racks

Max. 1

Modules per rack

Max. 8

Number of DP masters

Integrated

None

Via CP

1