Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual
Page 127

Technical data of CPU 31xC
6.4 CPU 313C-2 PtP and CPU 313C-2 DP
CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05
6-17
Technical data
CPU 313C-2 PtP
CPU 313C-2 DP
Communication functions
CPU 313C-2 PtP
CPU 313C-2 DP
PG/OP communication
Yes
Global data communication
Yes
•
Number of GD circuits
4
•
Number of GD packets
–
Sending stations
–
Receiving stations
Max. 4
Max. 4
Max. 4
•
Length of GD packets
–
Consistent data
max. 22 bytes
22 bytes
S7 basic communication
Yes (server)
•
User data per request
–
Consistent data
max. 76 bytes
76 bytes (for X_SEND or X_RCV)
64 bytes (for X_PUT or X_GET as the server)
S7 communication
•
As server
Yes
•
as client
Yes (via CP and loadable FBs)
•
User data per request
–
Consistent data
max. 180 bytes (with PUT/GET)
64 bytes
S5-compatible communication
Yes (via CP and loadable FCs)
Number of connections
Max. 8
can be used for
•
PG communication
–
Reserved (default)
–
Configurable
Max. 7
1
from 1 to 7
•
OP communication
–
Reserved (default)
–
Configurable
Max. 7
1
from 1 to 7
•
S7-based communication
–
Reserved (default)
–
Configurable
Max. 4
4
from 0 to 4
Routing
No
Max. 4
Interfaces
CPU 313C-2 PtP
CPU 313C-2 DP
1st interface
Type of interface
Integrated RS485 interface
Physics
RS 485
electrically isolated
No
Interface power supply (15 to 30 VDC)
Max. 200 mA
Functionality
•
MPI
Yes
•
PROFIBUS DP
No
•
Point-to-point communication
No