Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual
Page 164
Technical data of CPU 31xC
6.6 Technical data of the integrated I/O
CPU 31xC and CPU 31x, Technical data
6-54
Manual, Edition 08/2004, A5E00105475-05
Technical data
Permitted potential difference
•
between M
ANA
and M
internal
(U
ISO
)
75 VDC / 60 VAC
Insulation test voltage
600 VDC
Analog value generation
Resolution (including overdrive)
11 bits + signed bit
Conversion time (per channel)
1 ms
Settling time
•
with resistive load
0,6 ms
•
With capacitive load
1,0 ms
•
With inductive load
0.5 ms
Interference suppression, error limits
Crosstalk between the outputs
> 60 dB
Operational error limits (across the temperature range, in relation to output
range)
•
Voltage/current
± 1 %
Basic error limit (operational limit at 25 °C, in relation to output range)
•
Voltage/current
± 0,7 %
Temperature error (in relation to output range)
± 0.01 %/K
Linearity error (in relation to output range)
± 0,15 %
Repeat accuracy (in transient state at 25 °C, in relation to output range)
± 0,06 %
Output ripple; bandwidth 0 to 50 kHz (in relation to output range)
± 0,1 %
Status, interrupts, diagnostics
Interrupts
•
no interrupts when operated as standard
I/O
•
For using technological functions, please
refer to the
Technological Functions
Manual.
Diagnostics functions
•
no diagnostics when operated as
standard I/O
•
For using technological functions, please
refer to the
Technological Functions
Manual.
Actuator selection data
Output range (rated values)
•
Voltage
± 10 V
0 V to 10 V
•
Current
± 20 mA
0 mA to 20 mA
4 mA to 20 mA
Load resistance (within output rating)
•
For voltage outputs
–
Capacitive load
min. 1 kΩ
max. 0.1 μF
•
For current outputs
–
Inductive load
max. 300 Ω
0.1 mH