beautypg.com

7 routing – Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 38

background image

Communication

3.2 Communication services

CPU 31xC and CPU 31x, Technical data

3-10

Manual, Edition 08/2004, A5E00105475-05

GD resources of the CPUs

Table 3-4

GD resources of the CPUs

Parameters

CPU 31xC, 312, 314 CPU 315-2 DP,

315-2 PN/DP, 317

Number of GD circuits per CPU

Max. 4

Max. 8

GD packets transmitted per GD circuit

Max. 1

Max. 1

GD packets transmitted by all GD circuits

Max. 4

Max. 8

GD packets received per GD circuit

Max. 1

Max. 1

GD packets received by all GD circuits

Max. 4

Max. 8

Data length per GD packet

max. 22 bytes

max. 22 bytes

Consistency

max. 22 bytes

max. 22 bytes

Min. reduction ratio (default)

1 (8)

1 (8)

3.2.7

Routing

Properties

STEP 7 V5.1 + SP4 or higher allows you to access your S7 stations on all subnets with your

PG/PC, for example, to

download user programs

download a hardware configuration, or

perform debugging and diagnostic functions.

Note
When the CPU is used as intelligent slave, the routing function is only available when the

DP interface is set active. IN STEP 7, set the Test, Commission Routing check box on

the properties dialog of the DP interface. For detailed information, refer to the

Programming with STEP 7 manual, or directly to the STEP 7 Online Help