beautypg.com

4 status and error displays of the cpu 31x – Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 27

background image

Operating and display elements

2.2 Operating and display elements: CPU 31x

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

2-11

2.2.4

Status and error displays of the CPU 31x

General status and error displays

Table 2-6

General status and error displays of the CPU 31x

LED designation

Color

Meaning

SF

red

Hardware or software error.

DC5V

green 5-V power for the CPU and the S7-300 bus

FRCE

yellow LED is lit: Active force job

LED flashes at 2 Hz: Node flash test function (only CPUs with

firmware V2.2.0 or higher)

RUN

green CPU in RUN

The LED flashes during STARTUP at a rate of 2 Hz, and in HOLD

state at 0.5 Hz.

STOP

yellow CPU in STOP, or HOLD, or STARTUP

The LED flashes at 0.5 Hz when the CPU requests a memory reset,

and during the reset at 2 Hz.

Displays for the X1 and X2 interfaces

Table 2-7

Bus error displays of CPU 31x

CPU

LED designation

Color

Meaning

315-2 DP

BF

red

Bus error at DP interface (X2)

BF1

red

Bus error at interface 1 (X1)

317-2 DP

BF2

red

Bus error at interface 2 (X1)

BF1

red

Bus error at interface 1 (X1)

BF2

red

Bus error at interface 2 (X1)

LINK

green Active communication at interface 2 (X2).

31x-2 PN/DP

RX/TX

yellow Receive / Transmit data at interface 2 (X2)

Reference

CPU operating modes:

STEP 7 Online Help.

Information on CPU memory reset:

Operating instructions CPU 31xC and CPU31x,

Commissioning, Commissioning Modules, CP Memory Reset by means of Mode Selector

Switch

Evaluation of the LEDs upon error or diagnostic event:

Operating Instructions CPU 31xC

and CPU 31x, Test Functions, Diagnostics and Troubleshooting, Diagnostics with the

help of Status and Error LEDs