Ed -21 – Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual
Page 49
Communication
3.2 Communication services
CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05
3-21
Comparison of the System and Standard Functions of PROFINET IO and PROFIBUS DP
For CPUs with an integrated PROFINET interface, the table below provides you with an
overview of:
•
System and standard functions for SIMATIC that you may need to replace when
converting from PROFIBUS DP to PROFINET IO.
•
New system and standard functions
Table 3-6
New System Standard Functions of PROFINET IO and PROFIBUS DP and Those That
Must Be Replaced
Blocks
PROFINET IO
PROFIBUS DP
SFC13 (read diagnostic data of
a DP slave)
No
Substitute:
•
event-related: SFB 54
•
state-related: SFB 52
Yes
SFC58/59 (write/read data
record in I/O)
No (replacement: SFB53/52)
yes (but should already have
been replaced by SFB53/52 in
DPV1)
SFB52/53 (read/write data
record)
Yes
Yes
SFB54 (evaluate alarm)
Yes
Yes
SFC102 (read predefined
parameters)
No (replacement: SFB81)
Yes
new:
SFB81 (read predefined
parameters)
Yes
Yes
SFC5 (query start address of a
module)
No (replacement: SFC70)
Yes
new:
SFC70 (query start address of a
module)
Yes
Yes
SFC49 (query the slot belonging
to a logical address)
No (replacement: SFC71)
Yes
new:
SFC71 (query the slot belonging
to a logical address)
Yes
Yes