Technical data of CPU 31x

7.7 CPU 317-2 PN/DP

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

7-39

Technical data
Functionality

PROFINET

Yes

MPI

No

PROFIBUS DP

No

Point-to-point communication

No

Services

PG communication

Yes

OP communication

Yes

S7 communication

Max. configurable interconnections

Yes (with loadable FBs)

16

Routing

Yes

PROFINET IO

Yes

PROFINET CBA

Yes

PROFINET IO
Number of integrated PROFINET IO controllers

1

Number of connectable PROFINET IO devices

128

Max. user data consistency with PROFINET IO

256 bytes

Update Time

1 ms to 512 ms
The minimum value is determined by the set

communication portion for PROFINET IO, the

number of IO devices and the amount of

configured user data.

S7 protocol functions

PG functions

Yes

OP functions

Yes

Open IE communication via TCP/IP

Yes

GSD file

The latest GSD file is available at:
http://www.ad.siemens.de/support
in the Product Support area

Programming
Programming language

LAD/FBD/STL

Available instructions

See the Instruction List

Nesting levels

8

System functions (SFCs)

See the Instruction List

System function blocks (SFBs)

See the Instruction List

User program security

Yes

Dimensions

Mounting dimensions W x H x D (mm)

80 x 125 x 130

Weight