Technical data of CPU 31xC

6.6 Technical data of the integrated I/O

CPU 31xC and CPU 31x, Technical data

6-38

Manual, Edition 08/2004, A5E00105475-05

Value

1

Value

2

Value

3

. . .

Value

16

Value

17

Value

1

Value

2

Value

3

. . .

Value

16

Value

17

1.05 ms

1.05 ms

1.05 ms

1.05 ms

1.05 ms

1.05 ms

1.05 ms

1.05 ms

1.05 ms

1.05 ms

Example of a 60-Hz parasitic frequency suppression (integration time corresponds to 16.7 ms)

1 averaged measured value

1 averaged measured value

Cycle 1

Cycle 2

Figure 6-6

60 Hz interference suppression

Note
If the interference frequency is not 50/60 Hz or a multiple thereof, the input signal must be

filtered externally.

In this case, 400 Hz frequency suppression must be configured for the respective input. This

is equivalent to a "Deactivation" of the software filter.

Inputs not connected

The three inputs of a current/voltage analog output channel that is not connected should be

bypasses and connected to M

ANA

(pin 20 of the front connector). This ensures maximum

interference resistance for these analog inputs.

Outputs not connected

In order to disconnect unused analog outputs from power, you must disable and leave them

open during parameter assignment with STEP 7.

Reference

Details (visualization and processing of analog values, for example) are found in chapter 4 of

the

Module Data Reference Manual.