Technical data of CPU 31x
7.6 CPU 317-2 DP
CPU 31xC and CPU 31x, Technical data
7-30
Manual, Edition 08/2004, A5E00105475-05
Technical data
Number of connections
32
can be used for
•
PG communication
–
Reserved (default)
–
Configurable
Max. 31
1
1 to 31
•
OP communication
–
Reserved (default)
–
Configurable
Max. 31
1
1 to 31
•
S7-based communication
–
Reserved (default)
–
Configurable
Max. 30
0
0 to 30
Routing
Yes (max. 8)
Interfaces
1st interface
Type of interface
Integrated RS485 interface
Physics
RS 485
electrically isolated
Yes
Interface power supply
(15 to 30 VDC)
max. 200 mA
Functionality
•
MPI
Yes
•
PROFIBUS DP
Yes
•
Point-to-point communication
No
MPI
Services
•
PG/OP communication
Yes
•
Routing
Yes
•
Global data communication
Yes
•
S7 basic communication
Yes
•
S7 communication
–
As server
–
As client
Yes
No (but via CP and loadable FBs)
•
Transmission rates
Max. 12 Mbps
DP master
Services
•
PG/OP communication
Yes
•
Routing
Yes
•
Global data communication
No
•
S7 basic communication
No
•
S7 communication
No
•
Constant bus cycle time
Yes
•
SYNC/FREEZE
Yes
•
DPV1
Yes