Technical data of CPU 31xC

6.6 Technical data of the integrated I/O

CPU 31xC and CPU 31x, Technical data
Manual, Edition 08/2004, A5E00105475-05

6-51

6.6.8

Analog inputs

Introduction

This chapter contains the specifications for analog outputs of CPUs 31xC.
The table includes the following CPUs:

CPU 313C

CPU 314C-2 DP

CPU 314C-2 PtP

Technical data

Table 6-14 Technical data of analog inputs

Technical data
Module-specific data
Number of inputs

4 channels with current/voltage input
1 channel with resistance input

Cable length

Shielded

Max. 100 m

Voltage, currents, potentials
Resistance input

No-load voltage

Typically 2.5 V

Measurement current

Typically 1.8 mA to 3.3 mA

Electrical isolation

Between channels and the backplane bus

Yes

Between the channels

No

Permitted potential difference

Between inputs (AI

C

) and M

ANA

(U

CM

)

8.0 VDC

between M

ANA

and M

internal

(U

ISO

)

75 VDC / 60 VAC

Insulation test voltage

600 VDC

Analog value generation
Measurement principle

Actual value encoding (successive

approximation)

Integration time/conversion time/resolution (per channel)

Configurable

Yes

Integration time in ms

2,5 / 16,6 / 20

Permitted input frequency

Max. 400 Hz

Resolution (including overdrive)

11 bits + signed bit

Suppression of interference frequency f1

400 / 60 / 50 Hz