Technical data of CPU 31xC

6.6 Technical data of the integrated I/O

CPU 31xC and CPU 31x, Technical data

6-50

Manual, Edition 08/2004, A5E00105475-05

Technical data

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Data for the selection of an actuator for

standard DI

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Output voltage

For signal "1"

Min. L+ (-0.8 V)

Output current

For signal "1"

Rated value

Permitted range

0,5 A
5 mA to 600 mA

For signal "0" (residual current)

Max. 0.5 mA

Load impedance range

48 Ω to 4 kΩ

Lamp load

Max. 5 W

Parallel connection of 2 outputs

for redundant load control

Possible

for performance increase

Not possible

Controlling of digital inputs

Possible

Switching frequency

under resistive load

Max. 100 Hz

For inductive load to IEC 947-5, DC13

Max. 0.5 Hz

under lamp load

Max. 100 Hz

fast outputs under resistive load

Max. 2.5 kHz

Inductive breaking voltage limited internally to Typically (L+) - 48 V
Short-circuit protection of the output

Yes, electronic

Response threshold

Typically 1 A