beautypg.com

Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 134

background image

Technical data of CPU 31xC

6.5 CPU 314C-2 PtP and CPU 314C-2 DP

CPU 31xC and CPU 31x, Technical data

6-24

Manual, Edition 08/2004, A5E00105475-05

Technical data

CPU 314C-2 PtP

CPU 314C-2 DP

Communication functions

CPU 314C-2 PtP

CPU 314C-2 DP

PG/OP communication

Yes

Global data communication

Yes

Number of GD circuits

4

Number of GD packets

Sending stations

Receiving stations

Max. 4
Max. 4
Max. 4

Length of GD packets

Consistent data

max. 22 bytes
22 bytes

S7 basic communication

Yes

User data per request

Consistent data

max. 76 bytes
76 bytes (for X_SEND or X_RCV)
64 bytes (for X_PUT or X_GET as the server)

S7 communication

As server

Yes

as client

Yes (via CP and loadable FBs)

User data per request

Consistent data

max. 180 bytes (with PUT/GET)
64 bytes

S5-compatible communication

Yes (via CP and loadable FCs)

Number of connections

Max. 12

can be used for

PG communication

Reserved (default)

Configurable

Max. 11
1
from 1 to 11

OP communication

Reserved (default)

Configurable

Max. 11
1
from 1 to 11

S7-based communication

Reserved (default)

Configurable

Max. 8
8
from 0 to 8

Routing

No

Max. 4

Interfaces

CPU 314C-2 PtP

CPU 314C-2 DP

1st interface

Type of interface

Integrated RS485 interface

Physics

RS 485

electrically isolated

No

Interface power supply (15 to 30 VDC) Max. 200 mA
Functionality

MPI

Yes

PROFIBUS DP

No

Point-to-point communication

No