beautypg.com

7 digital outputs – Siemens Simatic S7-300 CPU 31xC and CPU 31x S7-300 User Manual

Page 158

background image

Technical data of CPU 31xC

6.6 Technical data of the integrated I/O

CPU 31xC and CPU 31x, Technical data

6-48

Manual, Edition 08/2004, A5E00105475-05

Technical data

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Data for the selection of an encoder for

standard DI

CPU 312C

CPU 313C

CPU 313C-2

CPU 314C-2

Input voltage

Rated value

24 VDC

For signal "1"

15 V to 30 V

For signal "0"

-3 V to 5 V

Input current

For signal "1"

Typically 9 mA

Delay of standard inputs

Configurable

Yes (0.1 / 0.5 / 3 / 15 ms)

You can reconfigure the input delay of the standard inputs during program

runtime. Please note that your newly set filter time may only take effect

after the previously set filter time has expired.

Rated value

3 ms

For using technological functions:
"Minimum pulse width/ minimum pause

between pulses at maximum counting

frequency"

48 μs

16 μs

16 μs

8 μs

Input characteristics curve

to IEC 1131, type 1

Connection of 2­wire BEROs

Possible

Permitted quiescent current

Max. 1,5 mA

6.6.7

Digital outputs

Introduction

This chapter contains the specifications for the digital outputs of CPUs 31xC.
The table includes the following CPUs:

under CPU 313C-2, the CPU 313C-2 DP and CPU 313C-2 PtP

under CPU 314C-2, the CPU 314C-2 DP and CPU 314C-2 PtP

Fast digital outputs

Technological functions use fast digital outputs.