Technical data of CPU 31x

7.3 CPU 314

CPU 31xC and CPU 31x, Technical data

7-10

Manual, Edition 08/2004, A5E00105475-05

Technical data
Number of function modules and communication

processors you can operate

FM

Max. 8

CP (PtP)

Max. 8

CP (LAN)

Max. 10

Time-of-day
Real-time clock

Yes (HW clock)

Buffered

Yes

Buffered period

Typically 6 weeks (at an ambient temperature of

104 °F)

Behavior of the clock on expiration of the

buffered period

The clock keeps running, continuing at the time-

of-day it had when power was switched off.

Accuracy

Deviation per day: < 10 s

Operating hours counter

1

Number

0

Value range

2

31

hours

(if SFC 101 is used)

Granularity

1 hour

Retentive

yes; must be manually restarted after every

restart

Clock synchronization

Yes

In the PLC

Master

On MPI

Master/slave

S7 signaling functions
Number of stations that can log in for signaling

functions (e.g. OS)

12
(depends on the number of connections

configured for PG / OP and S7 basic

communication)

Process diagnostics messages

Yes

Simultaneously enabled interrupt S blocks

Max. 40

Testing and commissioning functions
Status/control variables

Yes

Variables

Inputs, outputs, memory bits, DBs, timers,

counters

Number of variables

Of those as status variable

Of those as control variable

30
30
14

Forcing

Yes

Variables

Inputs/Outputs

Number of variables

Max. 10

Block status

Yes

Single step

Yes

Breakpoints

2

Diagnostic buffer

Yes