Technical data of CPU 31x
7.4 CPU 315-2 DP
CPU 31xC and CPU 31x, Technical data
7-16
Manual, Edition 08/2004, A5E00105475-05
Technical data
Diagnostic buffer
Yes
•
Number of entries (not configurable)
Max. 100
Communication functions
PG/OP communication
Yes
Global data communication
Yes
•
Number of GD circuits
8
•
Number of GD packets
–
Sending stations
–
Receiving stations
Max. 8
Max. 8
Max. 8
•
Length of GD packets
–
Consistent data
max. 22 bytes
22 bytes
S7 basic communication
Yes
•
User data per request
–
Consistent data
max. 76 bytes
76 bytes (for X_SEND or X_RCV)
64 bytes (for X_PUT or X_GET as the server)
S7 communication
Yes
•
As server
Yes
•
as client
Yes (via CP and loadable FBs)
•
User data per request
–
Consistent data
Max. 180 bytes (with PUT/GET)
64 byte (as the server)
S5-compatible communication
Yes (via CP and loadable FCs)
Number of connections
16
can be used for
•
PG communication
–
Reserved (default)
–
Configurable
Max. 15
1
1 to 15
•
OP communication
–
Reserved (default)
–
Configurable
Max. 15
1
1 to 15
•
S7-based communication
–
Reserved (default)
–
Configurable
Max. 12
12
0 to 12
Routing
Yes (max. 4)
Interfaces
1st interface
Type of interface
Integrated RS485 interface
Physics
RS 485
electrically isolated
No
Interface power supply
(15 to 30 VDC)
max. 200 mA