Rack pdu specifications – IBM PC Server/Enterprise Racks 42S User Manual
Page 162

154
Hardware Maintenance Manual: IBM PC Server/Enterprise Racks
Rack PDU specifications
When connected to a dedicated power source, the Rack PDU conforms to UL950, CSA
22.0-950, EN-60950, and IEC-950 standards. The following table contains the product
specifications for the Rack PDU:
Height
43 mm (1.7 in.)
Width
192 mm (7.5 in.)
Depth
221 mm (8.7 in.)
Weight
1.5 kg (3.2 lbs)
Operating temperatures
10
°
C–35
°
C (50
°
F–95
°
F) at 0–914 m (0–3000 ft)
10
°
C–32
°
C (50
°
F–90
°
F
°
)
at 914–2133 m (3000–7000 ft)
Operating humidity
8–80% (non-condensing)
Rated voltage
100–240 V ac, 15 A, single-phase
Rated frequency
50–60 Hz
Maximum power rating
3600 VA
Circuit breaker
Two-pole, 15 A with time-delay protection for up to 600 A
input current without nuisance tripping.
Power inlet
IEC 320-C20 inlet rated at 16 A (VDE) / 20 A (UL/CSA)
Power outlets
Seven IEC 320-C13 outlets rated at 10 A (VDE) / 15 A
(UL/CSA)
- PC Server/Enterprise Racks 9QS PC Server/Enterprise Racks 200 PC Server/Enterprise Racks 42P PC Server/Enterprise Racks 4QS PC Server/Enterprise Racks 4SB PC Server/Enterprise Racks 42E PC Server/Enterprise Racks 4QX PC Server/Enterprise Racks 900 PC Server/Enterprise Racks 42X PC Server/Enterprise Racks 9TX PC Server/Enterprise Racks 4SA PC Server/Enterprise Racks 9TS PC Server/Enterprise Racks 9QX