beautypg.com

Power requirements, Electrical grounding requirements – HP ProLiant DL100 Series Server DL100 Series User Manual

Page 19

background image

The maximum recommended ambient operating temperature (TMRA) for most server products is 35°C

(95°F). The temperature in the room where the rack is located must not exceed 35°C (95°F).

CAUTION:

To reduce the risk of damage to the equipment when installing third-party options:

Do not permit optional equipment to impede airflow around the server or to increase the
internal rack temperature beyond the maximum allowable limits.

Do not exceed the manufacturer’s TMRA.

Power requirements

Installation of this equipment must comply with local and regional electrical regulations governing the
installation of information technology equipment by licensed electricians. This equipment is designed to

operate in installations covered by NFPA 70, 1999 Edition (National Electric Code) and NFPA-75, 1992

(code for Protection of Electronic Computer/Data Processing Equipment). For electrical power ratings on

options, refer to the product rating label or the user documentation supplied with that option.

WARNING:

To reduce the risk of personal injury, fire, or damage to the equipment, do not

overload the AC supply branch circuit that provides power to the rack. Consult the electrical

authority having jurisdiction over wiring and installation requirements of your facility.

CAUTION:

Protect the server from power fluctuations and temporary interruptions with a

regulating uninterruptible power supply (UPS). This device protects the hardware from

damage caused by power surges and voltage spikes and keeps the system in operation
during a power failure.

When installing more than one server, you may need to use additional power distribution devices to

safely provide power to all devices. Observe the following guidelines:

Balance the server power load between available AC supply branch circuits.

Do not allow the overall system AC current load to exceed 80 percent of the branch circuit AC
current rating.

Do not use common power outlet strips for this equipment.

Provide a separate electrical circuit for the server.

Electrical grounding requirements

The server must be grounded properly for proper operation and safety. In the United States, you must
install the equipment in accordance with NFPA 70, 1999 Edition (National Electric Code), Article 250,

as well as any local and regional building codes. In Canada, you must install the equipment in

accordance with Canadian Standards Association, CSA C22.1, Canadian Electrical Code. In all other

countries, you must install the equipment in accordance with any regional or national electrical wiring
codes, such as the International Electrotechnical Commission (IEC) Code 364, parts 1 through 7.

Furthermore, you must be sure that all power distribution devices used in the installation, such as branch

wiring and receptacles, are listed or certified grounding-type devices.
Because of the high ground-leakage currents associated with multiple servers connected to the same
power source, HP recommends the use of a PDU that is either permanently wired to the building’s branch

circuit or includes a nondetachable cord that is wired to an industrial-style plug. NEMA locking-style plugs

or those complying with IEC 60309 are considered suitable for this purpose. Using common power outlet

strips for the server is not recommended.

Setup 19