HP SureStore 4215w User Manual
Page 91

3-37
Operating the Library
Using Online Drive Replacement
L
ibrary
O
perat
io
n
5. Press
NEXT
or
PREV
until
DRIVE
STATUS
displays, then press
ENTER
.
DRV
1
ON
GOOD
displays.
•
If the damaged tape is in drive 1, press
ENTER
.
•
If the damaged tape is in drive 2, press
NEXT
until
DRV
2
ON
GOOD
displays,
then press
ENTER
.
DRV
#
ON
GOOD
displays, where “#” is the drive number and
ON
GOOD
is
flashing.
6. Press
NEXT
until
DRV
#
OFF
FAILED
displays then press
ENTER
.
7.
CHANGE
CONFIRMED
displays briefly, then
ONLINE
REPAIR
*
displays.
Press
ENTER
.
8.
DRIVE
POWER
*
displays.
9. Press
NEXT
or
PREV
until
DRIVE
STATUS
displays, then press
ENTER
.
10. Press
NEXT
or
PREV
until
DRV
#
OFF
FAILED
displays (where “#” is the
number of the drive that was just taken off-line) then press
ENTER
.
11.
DRV
#
OFF
FAILED
displays, where “#” is the drive number and
OFF
FAILED
is flashing.
12. Press
NEXT
until
DRV
#
ON
GOOD
displays, then press
ENTER
.
13.
SETTING
UP
DRIVE
displays briefly while the drive communication tests run,
following by
CHANGE
CONFIRMED
and then
ONLINE
REPAIR
*
.
14. Press
CANCEL
twice to return to the drive numbers and status indicators (“ready”
state).
15. Try reading the damaged tape again.
•
If the tape can be read, back up data from the damaged cartridge to another
tape cartridge and discard the damaged one.
•
If the tape cannot be read, call your service representative.