HP SureStore 4215w User Manual

Page 91

background image

3-37

Operating the Library

Using Online Drive Replacement

L

ibrary

O
perat

io

n

5. Press

NEXT

or

PREV

until

DRIVE

STATUS

displays, then press

ENTER

.

DRV

1

ON

GOOD

displays.

If the damaged tape is in drive 1, press

ENTER

.

If the damaged tape is in drive 2, press

NEXT

until

DRV

2

ON

GOOD

displays,

then press

ENTER

.

DRV

#

ON

GOOD

displays, where “#” is the drive number and

ON

GOOD

is

flashing.

6. Press

NEXT

until

DRV

#

OFF

FAILED

displays then press

ENTER

.

7.

CHANGE

CONFIRMED

displays briefly, then

ONLINE

REPAIR

*

displays.

Press

ENTER

.

8.

DRIVE

POWER

*

displays.

9. Press

NEXT

or

PREV

until

DRIVE

STATUS

displays, then press

ENTER

.

10. Press

NEXT

or

PREV

until

DRV

#

OFF

FAILED

displays (where “#” is the

number of the drive that was just taken off-line) then press

ENTER

.

11.

DRV

#

OFF

FAILED

displays, where “#” is the drive number and

OFF

FAILED

is flashing.

12. Press

NEXT

until

DRV

#

ON

GOOD

displays, then press

ENTER

.

13.

SETTING

UP

DRIVE

displays briefly while the drive communication tests run,

following by

CHANGE

CONFIRMED

and then

ONLINE

REPAIR

*

.

14. Press

CANCEL

twice to return to the drive numbers and status indicators (“ready”

state).

15. Try reading the damaged tape again.

If the tape can be read, back up data from the damaged cartridge to another
tape cartridge and discard the damaged one.

If the tape cannot be read, call your service representative.