Environment, Power specification, Input power requirements – HP TC4100 User Manual

Page 126: Environment power specification

background image

124

Chapter 9

Specifications

Environment

The specifications listed below can vary if you install a mass storage device in your HP Server tc4100 that has
more stringent environmental limits. Ensure that the operating environment is suitable for all mass storage
devices in use.

Power Specification

Input Power Requirements

Table 9-6

displays the HP Server tc4100 input power requirements.

Table 9-5. Environmental Requirements

BTU

1845 BTU/hr maximum

Temperature

Operating 5° C to 35°C
(41°F to 95° F)
Non-operating –40° C to +65° C
(–40° F to +149° F)

Humidity

Operating 20% to 80% relative humidity
(non-condensing)
Non-operating 5% to 95% relative humidity
(non-condensing)

Altitude

Operating -30 to 3,045 m (10,000 ft)
Non-operating -30 to 12,180 m (40,000 ft)

Acoustic Emissions

Sound Level: (LpA) < 43 dB(A) bystander position

Table 9-6. Input Power Requirements

Input Voltage and Frequency

100-240 ±10%; 50/60 Hz

Maximum Inrush Current

8 AMPs peak (for 1 power supply) 120 VAC or
16 AMPs peak (for 2 power supplies)
16 AMPs peak (for 1 power supply) 240 VAC or
32 AMPs peak (for 2 power supplies)

Delayed Action Circuit Breaker
Recommended

North America: a 20 A minimum delayed action
circuit recommended for each 16 A power
distribution unit (PDU) that is connected to an HP
Server tc4100.
Europe (single server in a rack): a 16 A minimum
circuit with one IEC-MCB C-type breaker for
each 16 Amp PDU.
Europe (single server in a rack): a 16 A minimum
circuit with one IEC-MCB D-type breaker for
each 16 Amp PDU.

NOTE

Some local codes allow 16-amp service for a 16-amp device. Consult a qualified
electrician or local regulatory authority before beginning electrical site preparation.