ProSoft Technology 5105-103M-PDPS User Manual
Page 99

5105-103M-PDPS ♦ ProLinx Gateway
Reference
IEC 60870-5-103 Master to PROFIBUS Slave Gateway
User Manual
ProSoft Technology, Inc.
Page 99 of 144
November 24, 2010
Error
Description
603
Illegal session
604
Session is reserved
605
Session is not available
701
No memory to transmit message
702
ASDU not supported
703
Duplicate request
704
Illegal sector
705
Control mode is illegal
801
Partial stop request
802
Stop request failed
902
Negative COT in response
903
Session is offline
904
Session is disabled
905
Select confirmation received, waiting to execute
906
Execute confirmation has not been received.
103M Protocol Support
This section describes the portions of IEC 60870-5-103 protocol that are
supported by the module.
Note: Shaded areas are not supported by the module.
List of Type Identification Codes
In Monitor Direction
Type
Description
1
time-tagged message
2
time-tagged message with relative time
3
measurands l
4
time-tagged measurands with relative time
5
identification
6
time synchronization
8
general interrogation termination
9
measurands ll
10
generic data
11
generic identification
23
list of recorded disturbances
26
ready for transmission of disturbance data
27
ready for transmission of channel
28
ready for transmission of tags
29
transmission of tags
30
transmission of disturbance values
31