Pass-Through
The pass-through features allows you to page through the ProLinx data 4000
registers over the Profibus network, using mailbox commands. You can also use
mailbox commands to set and get time, and pass events. The following topics
describe the mailbox commands.
IMPORTANT NOTE: For these blocks to function properly over the Profibus network, the slave
must be configured for 100 words of input and 100 words of output, and the Pass-Through Events
parameter must be enabled in the configuration file, as shown in the following example.
Pass-Through Events : Y # Pass event messages through Profibus Interface
# (Y/N (N=Default))
Mailbox Commands
Start
Stop
Direction
Description
100
101
PLC to GW
Event Data
150
151
PLC to GW
Database write transfer
160
161
GW to PLC
Database read transfer
200
200
Both
Set Time
201
201
Both
Get Time
PLC = PROFIBUS master interface in PLC
GW = ProLinx Gateway
NOTES:
The block number for each device must be changed to trigger an operation.
The I/O data area is owned exclusively by only the PLC or GW.
A timeout must be implemented in the PLC in case the GW is not present.