ProSoft Technology 5105-103M-PDPS User Manual
Page 98

Reference
5105-103M-PDPS ♦ ProLinx Gateway
User Manual
IEC 60870-5-103 Master to PROFIBUS Slave Gateway
Page 98 of 144
ProSoft Technology, Inc.
November 24, 2010
Master Communication Module Error Codes
Error
Description
51
Physical Layer Error: Error transmitting message.
52
Physical Layer Error: Intercharacter timeout occurred before message fully
received
53
Physical Layer Error: Frame not entirely received before timeout condition
54
Physical Layer Error: Invalid Frame Length
101
Link Layer Error: Invalid checksum received
102
Link Layer Error: Address unknown to module
103
Link Layer Error: Link established
104
Link Layer Error: Link failed
105
Link Layer Error: Received Primary
106
Link Layer Error: FCB error discard
107
Link Layer Error: FCB error repeat
108
Link Layer Error: Invalid start character received
109
Link Layer Error: Invalid second character received
110
Link Layer Error: Invalid ending character received
111
Link Layer Error: Length mismatch error
112
Link Layer Error: Illegal function
113
Link Layer Error: No confirmation received
114
Link Layer Error: No ACK received
115
Link Layer Error: Sequence unknown
116
Link Layer Error: Out of sequence
117
Link Layer Error: Remote close
118
Link Layer Error: Unexpected ACK
119
Link Layer Error: Request cancelled
201
Application Layer Error: Length mismatch
202
Application Layer Error: Address unknown
203
Application Layer Error: Response late
251
RBE Error: Clock event buffer overflow
252
RBE Error: Event buffer overflow
271
Data Error: Address unknown
281
Control Error: Illegal operation
282
Control Error: Illegal value
283
Control Error: Not selected
301
Initialization Error: Database
302
Initialization Error: Out of Memory
401
Channel open error
501
Session Error: Database
502
Session Error: Configuration
601
No memory to receive message
602
Session not reserved