ProSoft Technology 5105-103M-PDPS User Manual
Page 46

Start Here
5105-103M-PDPS ♦ ProLinx Gateway
User Manual
IEC 60870-5-103 Master to PROFIBUS Slave Gateway
Page 46 of 144
ProSoft Technology, Inc.
November 24, 2010
1.9.1 From Address
0 to highest Status Data address
This field specifies the beginning internal database register address for the copy
operation. This address can be any valid address in the User Data Area or the
Status Data Area of the gateway.
1.9.2 To Address
0 to 3999
This parameter specifies the beginning destination register address for the copy
operation. This address must always be within the User Data registers area.
Take care to specify a destination address that will not overwrite data that has
been stored in memory by one of the communication protocols running on the
gateway.
1.9.3 Register Count
1 to 100
This parameter specifies the number of registers to copy.