ProSoft Technology 5105-103M-PDPS User Manual
Page 114

Reference
5105-103M-PDPS ♦ ProLinx Gateway
User Manual
IEC 60870-5-103 Master to PROFIBUS Slave Gateway
Page 114 of 144
ProSoft Technology, Inc.
November 24, 2010
Mailbox From PLC to Gateway
Start Byte
End Byte
Description
0
0
Block number of data in block
1
1
Block number of data requested
2
198
Data for block
199
199
Block number of data in block
Mailbox From GW to PLC
Start Byte
End Byte
Description
0
0
Block number of data in block
1
1
Last block number received from PLC
2
197
Data for block
198
198
Events in buffer (0 to 99)
199
199
Block number of data in block
Example Raw Database Exchange from PLC
Start Byte
End Byte
Description
0
0
150 (Raw data write)
1
1
160 (Raw data read)
2
3
Start register in database for write
4
5
Number of registers to write (1 to 94)
6
7
Start register in database for read
8
9
Number of registers to read (1 to 96)
10
197
Words to write to the database
198
198
Reserved for future use
199
199
150 (Raw data write)
Example Response Block From GW
Start Byte
End Byte
Description
0
0
160 (Raw data read)
1
1
150 (Raw data write)
2
3
Start register in database for read
4
5
Number of registers to read (1 to 96)
6
197
Words read from the database
198
198
Events in buffer (0 to 99)
199
199
160 (Raw data read)