Diagnostics and Troubleshooting
5105-103M-PDPS ♦ ProLinx Gateway
User Manual
IEC 60870-5-103 Master to PROFIBUS Slave Gateway
Page 62 of 144
ProSoft Technology, Inc.
November 24, 2010
Cfg Len is the configuration length for the slave with S as the pointer.
RCfg len is that received from the master with S as the pointer.
Ident is the PROFIBUS identification number for the module.
FDL SAP last PTR is the end of all the PDPS data in the SPC3 chip. A value
greater than 0xFF indicates a memory overflow problem.
Comm Failure mode is that from the configuration file as is the swapping of
input and output data.
2.4.2 Definition of Module’s Extended Diagnostics Data
The Extended Diagnostic Data is reported during startup and initialization
sequence when the master requests diagnostic data from the module. The
Extended Diagnostics is "Device Related" type providing status data (the
extended diagnostic bit 3 in standard diagnostic byte 1 is set = 0). The data
length is normally 14 (0E) bytes displayed in the following format:
Byte(s)
Description (HEX)
0
Extended Diagnostics length (normally 14 bytes (0E))
1 to 6
ASCII data for Product Version
7 to 10
ASCII data for Product Name
11
Value of Status Register [0] (page 64)
12
Value of Status Register [1] (page 67)
13
Module State (page 63)
Bytes 7 through 10 Data - Specific Product Code Value
Each ProLinx application has its own, unique product code. You can determine
the product code from the Version screen in the Configuration/Debug menu.
The following table lists the product codes for some ProLinx modules that
support the PDPS protocol.
Example Product
Example Product Code
5105-ASCII-PDPS
ASPS
5105-DFCM-PDPS
DFPS
5105-DH485-PDPS
D4PS
5105-DNPM-PDPS
DMPS
5105-DNPS-PDPS
D3PS
5105-101S-PDPS
ISPS
5105-103M-PDPS
PSI3
5105-MCM-PDPS
PDSM