ProSoft Technology 5105-103M-PDPS User Manual
Page 121

5105-103M-PDPS ♦ ProLinx Gateway
Reference
IEC 60870-5-103 Master to PROFIBUS Slave Gateway
User Manual
ProSoft Technology, Inc.
Page 121 of 144
November 24, 2010
Bit 0
Offline/Passive-idle
0 = SPC3 exits offline and goes to passive-idle. The idle timer and Wd timer
go offline.
1= SPC3 exits offline and goes to passive-idle. The idle timer and Wd timer
are started.
Bit 4, 5
10 = Data Exchange State is Normal. The SPC3 has a correct configuration.
Module State: Word 10310 Byte 0
Indicates the current state of the module.
0 = Normal Operation
1 = Shutdown
2 = File Transfer
3 = SPC3 ASIC problem
4 = Not in data exchange
Last Global Command: Word 10310 Byte 1
The value of the last global command code received from the master.
Bit
Designation
Significance
0
Reserved
1
Clear_Data
With this command the ASCI output data is deleted in data transfer
buffer and is changed to next transfer data buffer contents.
2
Unfreeze
With "Unfreeze": freezing input data is cancelled.
3
Freeze
The ASCI input data is fetched from next transfer buffer to data
transfer buffer and frozen. New input data is not fetched again until
the master sends the next "Freeze" command.
4
Unsync
The "Unsync" command cancels the "Sync" command.
5
Sync
The ASCI output data transferred with a WRITE_READ_DATA
telegram is changed from data transfer buffer next state buffer. The
following transferred output data is kept in data transfer buffer until
the next "Sync" command is given.
6,7
Reserved
The Reserved designation specifies that these bits are reserved for
future function expansions.
PROFIBUS Input Counter: 10311
Input counter is incremented each time the input data is updated.
PROFIBUS Output Counter: Word 10312
Output counter is incremented each time the output data is updated.
Words 10313 to 10399
No valid data