C1/C2 Poll Count Pend
0 to 65535
This parameter sets the maximum number of Class 1 and Class 2 polls
performed on this session before trying the next session. This parameter
prevents a session from monopolizing the communication port.
Class 1 Polls
0 to 100
This parameter sets the maximum number of Class 1 polls performed on this
session before switching to another session. This parameter prevents a session
from monopolizing the communication port.
Class 1 Pend Delay
0 to 4,294,967,295 (two raised to the power of 32, minus one) milliseconds
This parameter sets the minimum number of milliseconds to delay between Class
1 polls for pending data.
Class 2 Pend Delay
0 to 4,294,967,295 (two raised to the power of 32, minus one) milliseconds
This parameter sets the minimum number of milliseconds to delay between Class
2 polls for pending data.
Class 1 Poll Delay
0 to 4,294,967,295 (two raised to the power of 32, minus one) milliseconds
This parameter sets the minimum number of milliseconds to delay between each
Class 1 poll.
Class 2 Poll Delay
0 to 4,294,967,295 (two raised to the power of 32, minus one) milliseconds
This parameter sets the minimum number of milliseconds to delay between each
Class 2 poll.
Auto Clock Req Mode
0=Sync Only, 1=Load delay/sync, 2=Acquire delay/load delay/sync
This parameter specifies the method used to perform automatic clock
synchronization. 0 performs a synchronization without delay, 1 performs
synchronization using the fixed Propagation Delay and 2 computes the delay and
use this value when synchronization takes place.
Propagation Delay
0 to 65535
This parameter sets the fixed propagation delay to be utilized if the Auto Clock
Req Mode parameter is set to a value of 1.