November 24, 2010
Last Global Command
The value of the last global command code received from the master.
Bit
Designation
Significance
0
Reserved
1
Clear_Data
With this command the ASCI output data is deleted in data transfer
buffer and is changed to next transfer data buffer contents.
2
Unfreeze
With "Unfreeze": freezing input data is cancelled.
3
Freeze
The ASCI input data is fetched from next transfer buffer to data
transfer buffer and frozen. New input data is not fetched again until
the master sends the next "Freeze" command.
4
Unsync
The "Unsync" command cancels the "Sync" command.
5
Sync
The ASCI output data transferred with a WRITE_READ_DATA
telegram is changed from data transfer buffer next state buffer. The
following transferred output data is kept in data transfer buffer until
the next "Sync" command is given.
6,7
Reserved
The Reserved designation specifies that these bits are reserved for
future function expansions.